MR-2900 Operator’s Manual
14
EEPROM failure The memory chip containing the configuration information is not working
correctly. It will need to be erased. This requires a Level 9 passcode.
Erasing the EEPROM will lose ALL information in the EEPROM. This
includes the configuration information, the panel serial number and the
archive. Be sure to record this information before you erase the
EEPROM. Contact a service representative for help and a Level 9
passcode.
not enough EEPROM
to save addressable
settings
The panel has a 64k EEPROM and is running an MR2 program. The
addressable device bypasses and the manual operation of control
modules requires a 256k EEPROM for the settings to be retained when
the panel is rebooted. Note: This will not cause a common trouble on
the panel.
program mismatch The version number stored in the EEPROM is different from the version
number in the program. Either reload the old program or erase the
EEPROM. Erasing the EEPROM requires Privilege Level 9. Erasing the
EEPROM will lose ALL information in the EEPROM. This includes the
configuration information, the panel serial number and the archive. Be
sure to record this information before you erase the EEPROM. Contact
a service representative for help and a Level 9 passcode.
hardware mismatch The hardware listed in the database does not match the hardware listed
in the panel. Correct the database and reload.
no database loaded The panel does not have a database in memory. Load a database into
the panel.
wrong database
version or database
mismatch
The database is the incorrect version for the operating program running.
Download a database with the same version number as the operating
program.
no database for
this panel
The panel contains a valid database, but the database does not contain
the information for this panel. Either change the panel ID to the correct
value, or load a database that includes the panel's ID.
CoProcessor ?..?
off line
This is a major error. The CoProcessor for the circuits listed (1..8,
9..16, or 17..24) is not communicating with the main CPU. This
message will be repeated for each CoProcessor that is off-line. Devices
are not being monitored by the system. If a reboot of the MR-2900 does
not fix the problem, the addressable input module for those circuits will
need to be replaced.
CoProcessor ?..?
memory overflow
The CoProcessor for the addressable circuits listed (1..8, 9..16, or
17..24) has had a memory overflow. A reboot of the MR-2900 should be
done to correct any problems. This message will be repeated for each
CoProcessor that has overflowed.
low battery The battery needs recharging or replacement.
battery charger not
calibrated
The battery charger needs to be calibrated to provide proper
supervision of the batteries. To calibrate the charger, disconnect the
batteries and select PROGRAM/BATTERY/CALIBRATE from the LCD
menu.
Message Description
thank