MR-2900 Operator’s Manual
13
Smoke Detector and Contact Device Circuit: 000 - Wiring Fault
001 - Smoke Detector
002 - Contact Device
Comlink 1 (Zone 51): Unit Network ID number
Comlink 3 (Zone 53): Unit ID number
Note: Only MR-2614, MR-2644, MR2801-MR and MR-2806-MR use IDs other than 000.
Addressable Module Comlink (Zone 59): 001 - Circuits 1 to 8
002 - Circuits 9 to 16
003 - Circuits 17 to 24
Output Supervision (Zone 60): Output Circuit Number
Auxiliary Power Supervision (Zone 61): Auxiliary Power Circuit Number
Program Re-start (Zone 69): 000 - Power On/Hard reboot
001 - Watchdog
002 - Clock Monitor
003 - Illegal Instruction
004 - Unused Interrupt
005 - Orphan Interrupt
Privilege Level (Zone 80): Level Set
Switch (Zone 83): Switch Number
Hot Key Activation (Zone 90): Function Number of the Hot key pressed
Memory Overflow (Zone 91): 000 - MR-2900 panel
001 - CoProcessor for circuits 1..8
002 - CoProcessor for circuits 9..16
003 - CoProcessor for circuits 17..24
Network Reboot (Zone 92): Unit ID of panel broadcasting the command
Network Reboot Required (Zone 94): Unit ID of panel generating the Network Reboot
Required trouble
Network Reboot Required Why (Zone 95): 001 - network
002 - network
003 - port 3
006 - negative counter
008 - memory overflow
009 - co-processor memory overflow
All Others: Always 000
2.3 Miscellaneous Troubles
This is a list of all possible messages that can be displayed by Miscellaneous Trouble on the LCD.
Only those conditions that are in trouble will be shown. Some of the messages are always
displayed if the panel is in Test Mode.
Message Description
PROGRAM checksum The memory chip containing the operating program has an error in it.
Reloading the operating program will correct this problem. If this error
keeps reoccurring, the unit will need replacement.
EEPROM checksum The memory chip containing the configuration information has an error
in it. Changing a value of an item set through the LCD menu will cause
the panel to create a new checksum. If this error keeps reoccurring, the
unit will need replacement.
DATABASE checksum The memory chip containing the downloaded database has an error in
it. Reloading the database will correct this problem. If this error keeps
occurring, the unit will need replacement.
thank